FHT7 — 7" Touch Wireless Panel
7" Touchscreen Panel — compact installations · 1.5 km line-of-sight range
About this model
The wireless fire alarm and detection systems models 21026, 21028, 21029 and 21030 were developed to facilitate installation, maintenance, and layout changes;
Uses the AC electrical grid as power source, but has internal rechargeable battery for power backup, with 24-hour autonomy, with wireless communication radio with 2.4 GHz operating frequency and ISM band.
Feature a fully optimized system, superior design wrapped in extreme robustness and ease;
High performance, created to enhance user experience with hardware specifically developed for absolute control of Firebee system components;
Device Power Supply Data
:: Electrical Characteristics
Input Voltage: 120 ~ 240 VAC
Minimum Electrical Power: 8 W
Maximum Electrical Power: 14 W
Maximum Electrical Current: 0.14 Amperes
:: Backup Power Supply
Batteries: 01 unit of 12V / 12 Ah
Battery runtime: 24 hours (500 mA)
Average battery life: 24 months
Device Communication Data
:: Coverage Distances
Network Topology: Mesh
Line-of-sight range: 1500 m (1.5km)
Range with obstacles: 50 - 1500 m - Follow calculation rules for projects
Industrial Safety and Topology: ✅
Network with Point Redundancy: ✅
Network Shadowing Rule: ✅
Network with Clustering Mode: ✅
Wi-Fi Protocol: No
Suffers Wi-Fi interference?: No
:: Network Characteristics
Operating Frequency:
Band Type: ISM (Industrial Scientific and Medical)
Signal Modulation: O-QPSK
Channels: 11 to 26 (24 to 26 dedicated)
Antenna Gain: 5dBi
Transfer Rate: 256 Kbps
:: Data Security
Data Encryption: 128 bits
Encryption Mode: CCM mode (counter with cipher block chaining message authentication code; counter with CBC-MAC)
Device binding by MAC Address: ✅
Dedicated recording key: ✅
Unique addressing rule compliance: ✅
:: 12x greater range compared to previous generation (WB) - From 120 to 1500 meters